    This versatile 2-wire transmitter accepts a range of standard input types, and outputs a 4-20mA loop. USB programming is hassle free, and takes less than a minute using Define ToolBox.

    • 2-wire universal transmitter (DIN-mount, isolated)
    • Current, voltage, thermocouple, RTD and potentiometer input
    • Loop powered, 4-20mA output
    • LED indicator for error notification
    • Potentiometer for fine offset adjustment of current output

    Easy USB programming using Define ToolBox

    • No power supply or calibrator required
    • Uses the universal USB Bridge Key (sold separately) for PC connection
    CE
    Universal Input
     
    Configuration
    2 wire
    Number of universal inputs
    1 isolated universal input, full input specifications below
    Power
     
    Power supply
    10.5-36V DC
    Supply voltage sensitivity
    <±0.005%/V FSO
    General Specifications
     
    Accuracy
    ≤ ±0.1% of span
    Accurate to
    <±0.03% FSO typical
    Ambient drift
    <±0.003%/°C FSO typical
    Isolation test voltage
    Between input and output: 3750V AC for 1min
    Noise immunity
    125dB CMRR avg (2.0kV DC limit)
    RF immunity
    <1% effect FSO typical
    Maximum load
    1,200Ω (at 20mA with 36V input)
    Linearization tables
    32-point flexible linearization available
    Response time
    400msec typical (10-90% 300msec typical)
    Thermocouple Input
     
    Thermocouple types
    B, E, J, K, N, R, S, T
    Input impedance
    1MΩ min
    T/C lead resistance
    100Ω max
    Cold junction compensation
    -4 to 194°F (-20 to 90°C)
    CJC error
    <±1°C
    Accuracy
    E, J, K, N, T: <±1°C. B, R, S: <±2°C
    Ambient drift
    E, J, K, N, T: <±0.05°C. B, R, S: <±0.2°C
    Sensor break output drive
    Function high upscale/low downscale
    USB programmable zero
    0–±99% of the span
    RTD Input
     
    RTD input type
    PT100 or PT1000 DIN 3-wire type (2-wire can be used with off set calibration)
    Lead wire resistance

    PT100: 10Ω/wire max. PT1000: 5Ω/wire max
    0.02% FSO off set error per Ω of lead resistance.
    Sensor current
    0.15mA nominal
    Sensor break output drive
    Function high upscale/low downscale
    USB programmable zero
    0–±99% of the span
    USB programmable span
    –328 to 1562°F (–200 to 850°C)
    Linearity (PT100)
    0.02% FSO for span inputs ≤200°C. 0.1% FSO for span inputs ≤850°C
    Linearity (PT1000)
    0.02% FSO for span inputs ≤200°C. 0.2% FSO for span inputs ≤520°C
    Other available RTD types
    JIS, PT392, CN10
    Current Input
     
    USB programmable zero
    0–±99% of the span
    Field programmable span
    1μA–24mA DC
    Input impedance
    10Ω
    Max over-range
    50mA DC continuous
    Linearity & repeatability
    <±0.02% FSO typical
    Voltage Input
     
    USB programmable zero
    0–±99% of the span
    USB programmable span
    100mV to ±10V DC (bipolar)
    Input impedance
    300kΩ min
    Maximum over voltage
    60V DC continuous
    Linearity & repeatability
    <±0.02% FSO typical
    Potentiometer Input
     
    Potentiometer input
    3-wire potentiometer
    Excitation voltage
    1.2V DC
    Potentiometer resistance

    0–2KΩ low pot, 0–1MΩ high pot
    Field programmable zero
    0–90% of the span
    Field programmable span
    0.1–100%
    Linearity & repeatability
    <±0.02% FSO typical
    Analog Output (Retransmission)
     
    Analog output type
    4-20mA or 20-4mA (loop powered)
    Output load resistance
    650Ω at 24V DC (50Ω/V above 10.5V DC)
    Max output current
    Limited to < 28mA (emission and immunity)
    Programming
     
    Define ToolBox
    Simple programming using Define ToolBox (requires Bridge Key, sold separately)
    Construction
     
    Casing
    35mm DIN mount case
    Dimensions (H x W x D)
    3.11 x 0.79 x 2.68" (79 x 20 x 68mm)
    LED indication
    Flashing=Normal, On=Fault
    Potentiometer
    For fine offset adjustment of current output
    Environmental Conditions
     
    Operating temperature
    -4 to 185°F (-20 to 85°C)
    Storage temperature
    -4 to 185°F (-20 to 85°C)
    Operating humidity
    5–85%RH max (non-condensing)
    Certifications & Compliances
     
    EMC
    EN61326 (Emissions); EN61326 (Immunity); EN61010-1 (Safety)

    TM-2DLI Manual TM-2DLI Manual 15V11, 09-Oct-2015 | (334 KB)

    Define ToolBox

    Define ToolBox

    Smart, simple software to program your non-Zen series products

    Use Define ToolBox software to program your non-Zen series product via your PC. It configures:

    It offers a simple interface for connecting to your compatible device, and a range of flexible configuration options, including an extensive library of pre-calibrated ranges and linearization tables for advanced scaling.

    TM-2DLI